EasyManua.ls Logo

INFOSEC Nomad Combo C2 - Fault Reference Code

INFOSEC Nomad Combo C2
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INFOSEC UPS SYSTEM 4 rue de la Rigotière 44700 Orvault France www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 05 14 AA 59 203 02
66
Fault Reference Code
Fault Code
Fault Event
Icon on
01
The fan is locked when inverter is off.
02
Over temperature
03
Battery voltage is too high
04
Battery voltage is too low
05
Output short circuited or over temperature is detected
by internal converter components.
06
Output voltage is abnormal. (For 1K/2K/3K model)
Output voltage is too high. (For 4K/5K model)
07
Overload time out
08
Bus voltage is too high
09
Bus soft start failed
11
Main relay failed
51
Over current or surge
52
Bus voltage is too low
53
Inverter soft start failed
55
Over DC voltage in AC output
56
Battery connection is open
57
Current sensor failed
58
Output voltage is too low
NOTE: Fault codes 51, 52, 53, 55, 56, 57 and 58 are only available in 4K/5K model.

Table of Contents