5 Parameter Table
- 31 -
Para. No. Para. Name Setting Range Default Comms. Address
F3-01 Torque boost
0.0%: automatic torque boost
0.1% to 30%
0.0% 0xF301/0x0301
F3-02 Cut-off frequency of torque boost 0.00 Hz to maximum frequency 50.00 Hz 0xF302/0x0302
F3-03 Multi-point V/F frequency 1 0.00 Hz to F3-05 0.00 Hz 0xF303/0x0303
F3-04 Multi-point V/F voltage 1 0.0% to 100.0% 0.0% 0xF304/0x0304
F3-05 Multi-point V/F frequency 2 F3-03 to F3-07 0.00 Hz 0xF305/0x0305
F3-06 Multi-point V/F voltage 2 0.0% to 100.0% 0.0% 0xF306/0x0306
F3-07 Multi-point V/F frequency 3 F3-05 to rated motor frequency(F1-04) 0.00 Hz 0xF307/0x0307
F3-08 Multi-point V/F voltage 3 0.0% to 100.0% 0.0% 0xF308/0x0308
F3-09 Slip compensation gain 0.0% to 200.0% 0.0% 0xF309/0x0309
F3-10 V/F over-excitation gain 0 to 200 64 0xF30A/0x030A
F3-13
Voltage source for V/F
separation
0: Set by F3-14
1: AI
2: External operating panel
4: Pulse reference (DI4)
5: Multi-reference
6: Simple PLC
7: PID reference
8: Serial comms.
100.0% corresponds to the rated
motor voltage.
0 0xF30D/0x030D
F3-14
Digital setting of voltage for V/F
separation
0 V to rated motor voltage 0 V 0xF30E/0x030E
F3-15
Voltage rise time of V/F
separation
0.0 to 1000.0s 0.0s 0xF30F/0x030F
F3-16
Voltage decline time of V/F
separation
0.0 to 1000.0s 0.0s 0xF310/0x0310
F3-17
Stop mode selection for V/F
separation
0: Frequency and voltage declining to 0
independently
1: Frequency declining after voltage declines to 0
0 0xF311/0x0311
F3-18 Current limit level 50% to 200% 150% 0xF312/0x0312
F3-19 Current limit selection
0: Disabled
1: Enabled
1 0xF313/0x0313
F3-20 Current limit gain 0 to 100 20 0xF314/0x0314
F3-21
Compensation factor of speed
multiplying current limit level
0 to 200% 50% 0xF315/0x0315
F3-22 Voltage limit 330.0 to 800.0 V
Single phase
: 390.0 V
Three phase:
760.0V
0xF316/0x0316
F3-23 Voltage limit selection
0: Disabled
1: Enabled
1 0xF318/0x0317
F3-24 Frequency gain for voltage limit 0 to 100 50 0xF318/0x0318
F3-25 Voltage gain for voltage limit 0 to 100 30 0xF319/0x0319
F3-26
Frequency rise threshold during
voltage limit
0 to 50 Hz 5 Hz 0xF31A/0x031A
F3-27 Slip compensation time constant 0.1 to 10.0s 0.5 0xF31B/0x031B