5 Parameter Table
- 32 -
Para. No. Para. Name Setting Range Default Comms. Address
Group F4: Input Terminals
F4-00 DI1 function selection
0: No function
1: Forward run (FWD)
2: Reverse run (REV)
3: Three-wire control
4: Forward jog (FJOG)
5: Reverse jog (RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset (RESET)
10: RUN disabled
11: External fault normally-open input
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
16: Terminal 1 for acceleration/deceleration time
selection
18: Frequency reference setting channel
switchover
19: UP and DOWN setting clear (terminal,
operating panel)
20: Command source switchover
21: Acceleration/Deceleration prohibited
22: PID disabled
23: PLC state reset
30: Pulse input as frequency reference (On
MD200XXX model, it is valid for DI4 terminal ;
On MD200XXX-NC model), it is valid for DIO
terminal)
32: Immediate DC injection braking
33: External fault normally-closed input
34: Frequency modication enabled
35: PID operation direction reverse
36: External stop 1
37: Command source switchover 2
38: PID integral disabled
39: Switchover between main frequency
reference and preset frequency
40: Switchover between auxiliary frequency
reference and preset frequency
43: PID parameter switchover
47: Emergency stop (ES)
48: External stop 2
49: Deceleration DC injection braking
50: Clear running time this time
51: Two-wire control/ Three-wire control
52: Reverse running prohibited
1 0xF400/0x0400
F4-01 DI2 function selection 4 0xF401/0x0401
F4-02 DI3 function selection 9 0xF402/0x0402
F4-03 DI4 function selection 12 0xF403/0x0403
F4-04
DIO terminal input function
selection (only used on
MD200XXX-NC model)
F4-10 DI lter time 0.000s to 1.000s 0.010s 0xF40A/0x040A
F4-11 Terminal I/O control mode
0: Two-wire control mode 1
1: Two-wire control mode 2
2: Three-wire control mode 1
3: Three-wire control mode 2
0 0xF40B/0x040B
F4-12 Terminal UP/DOWN rate 0.001 to 65.535 Hz/s 1.000 Hz/s 0xF40C/0x040C