5 Parameter Table
- 33 -
Para. No. Para. Name Setting Range Default Comms. Address
F4-13 AI curve1 min. input 0.00 V to F4-15 0.00 V 0xF40D/0x040D
F4-14
Corresponding percentage of AI
curve 1 min. input
-100.00% to 100.0% 0.0% 0xF40E/0x040E
F4-15 AI curve 1 max. input F4-13 to 10.00 V 10.00 V 0xF40F/0x040F
F4-16
Corresponding percentage of
AIcurve1 max. input
-100.00% to 100.0% 100.0% 0xF410/0x0410
F4-17 AI1ltertime 0.00s to 10.00s 0.10s 0xF411/0x0411
F4-18 AI curve 2 min. input 0.00 V to F4-20 0.00 V 0xF412/0x0412
F4-19
Corresponding percentage of AI
curve 2 min. input
-100.00% to 100.0% 0.0% 0xF413/0x0413
F4-20 AI curve 2 max. input F4-18 to 10.00 V 10.00 V 0xF414/0x0414
F4-21
Corresponding percentage of AI
curve 2 max. input
-100.00% to 100.0% 100.0% 0xF415/0x0415
F4-22
External operating panel
potentiometer lter time
0.00 to 10.00s 0.10s 0xF416/0x0416
F4-28 Pulse min. input 0.00 kHz to F4-30 0.00 kHz 0xF41C/0x041C
F4-29
Corresponding percentage of
pulse min. input
-100.00% to 100.0% 0.0% 0xF41D/0x041D
F4-30 Pulse max. input F4-28 to 20.00 kHz 50.00 kHz 0xF41E/0x041E
F4-31
Corresponding percentage of
pulse max. input
-100.00% to 100.0% 100.0% 0xF41F/0x041F
F4-32 Pulse lter time 0.00s to 10.00s 0.10s 0xF420/0x0420
F4-33 AI curve selection
External operating
panel potentiometer
curve selection
1: Curve 1 (two-point,
see F4-13 to F4-16)
2: Curve 2 (two-point,
see F4-18 to F4-21)
AI curve selection
1: Curve 1 (two-point,
see F4-13 to F4-16)
2: Curve 2 (two-point,
see F4-18 to F4-21)
21 0xF421/0x0421