5 Parameter Table
- 35 -
Para. No. Para. Name Setting Range Default Comms. Address
Group F5: Output Terminals
F5-02 Relay (T/A-T/C) function selection
0: No output
1: AC drive running
2: Fault output
3: Frequency level detection 1 output
4: Frequency reached
5: Zero-speed running (no output at stop)
6: Motor overload pending
7: AC drive overload pending
11: PLC cycle completed
12: Accumulative running time reached
13: Frequency limited
15: Ready for RUN
17: Frequency upper limit reached
18: Frequency lower limit reached (no output at
stop)
19: Undervoltage
20: Communication setting
24: Accumulative power-on time reached
26: Frequency 1 reached
28: Current 1 reached
30: Timing reached
31: AI input exceeding limit
32: Load lost
33: Reverse running
34: Zero current
36: Output current exceeding limit
37: Frequency lower limit reached (having output
at stop)
38: Alarm output
40: Current running time reached
41: Fault output
2 0xF502/0x0502
F5-04
DIO terminal output function
selection (only used on
MD200XXX-NC model)
0 0xF504/0x0504
F5-07 AO function selection
0: Running frequency
1: Frequency reference
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: Pulse input
7: AI
8: External operating panel potentiometer
10: Length
11: Count value
12: Communication reference
13: Motor speed
14: Output current
15: Output voltage
16: Motor output torque (actual value)
0 0xF507/0x0507
F5-10 AO zero offset coefcient -100.0% to 100.0% 0.0% 0xF50A/0x050A
F5-11 AO gain -10.00 to 10.00 1.00 0xF50B/0x050B
F5-18 Relay1outputdelay 0.0 to 3600.0s 0.0s 0xF512/0x0512
F5-20 DIO output delay 0.0 to 3600.0s 0.0s 0xF514/0x0514