5 Parameter Table
- 36 -
Para. No. Para. Name Setting Range Default Comms. Address
F5-22 DO active mode selection 1
Relay 1 active
mode:
0: Positive logic
1: Negative logic
Reserved
DIO active mode:
0: Positive logic
1: Negative logic
Reserved
0000 0xF516/0x0516
Group F6: Start/Stop Control
F6-00 Start mode
0: Direct start
1: Catching a spinning motor
0 0xF600/0x0600
F6-01
Mode of catching a spinning
motor
0: From stop frequency
1: From 50 Hz
2: From maximum frequency
0 0xF601/0x0601
F6-03 Start frequency 0.00 to10.00 Hz 0.00 Hz 0xF603/0x0603
F6-04 Start frequency holding time 0.0 to 100.0s 0.0s 0xF604/0x0604
F6-07 Acceleration/Deceleration mode
0: Linear acceleration/deceleration
1: Static S-curve acceleration/deceleration
2: Dynamic S-curve acceleration/deceleration
0 0xF607/0x0607
F6-08
Time proportion of S-curve start
segment
0.0% to (100.0% –F6-09) 30.0% 0xF608/0x0608
F6-09
Time proportion of S-curve end
segment
0.0% to (100.0% –F6-08) 30.0% 0xF609/0x0609
F6-10 Stop mode
0: Decelerate to stop
1: Coast to stop
0 0xF60A/0x060A
F6-11
DC injection braking 2 start
frequency
0.00 Hz to maximum frequency 0.00 Hz 0xF60B/0x060B
F6-12 DC injection braking 2 delay time 0.0 to 100.0s 0.0s 0xF60C/0x060C
F6-13 DC injection braking 2 level 0% to 100% 50% 0xF60D/0x060D
F6-14 DC injection braking 2 active time 0.0 to 100.0s 0.0s 0xF60E/0x060E
F6-21 Demagnetization time 0.00s to 5.00s 0.5s 0xF615/0x0615
F6-22 Min. output frequency 0.00 Hz to F6-11 0.00 Hz 0xF616/0x0616
F6-23 Reserved by manufacturer 1 to 100 10 0xF617/0x0617