5 Parameter Table
- 37 -
Para. No. Para. Name Setting Range Default Comms. Address
Group F7: Keypad Operation and LED Display
F7-00 LED default display check
0: Disabled
1: Enabled
0 0xF700/0x0700
F7-01 MF.K key function selection
0: MF.K key disabled
1: Switchover from remote control (terminal or
communication) to keypad control
2: Switchover between forward rotation and
reverse rotation
3: Forward jog
4: Reverse jog
5: Parameter display mode switchover
0 0xF701/0x0701
F7-02 STOP/RESET key function
0: STOP/RESET key enabled only in keypad
control
1: STOP/RESET key enabled in any operation
mode
1 0xF702/0x0702
F7-03
LED display running parameters
1
0000 to FFFF
7 6 5 4 3 2 1 0
Running frequency (Hz)
Frequency reference (Hz)
Bus voltage (V)
Output voltage (V)
Output current (A)
Output power (kW)
Output torque (%)
DI state (V)
15 14 12 11 10 9 8
DO state
AI voltage (V)
Count value
Length value
Load speed display
PID reference
13
Reserved
External operating panel
potentiometer voltage (V)
001F 0xF703/0x0703
F7-04
LED display running parameters
2
0000 to FFFF
7 6 5 4 3 2 1 0
PID feedback
PLC stage
Pulse reference (kHz)
Feedback speed (Hz)
Remaining running time (min)
AI voltage before correction (V)
External operating panel potentiometer
voltage before correction (V)
Reserved
15 14 12 11 10 9 8
PLC stage
Pulse reference (kHz)
Length value
Reserved
13
Load speed
PID reference
Reserved
Reserved
0000 0xF704/0x0704