Para. No. Para. Name Setting Range Default Comms. Address
F8-13 Reverse RUN selection
0: Disabled
1: Enabled
0 0xF80D/0x080D
F8-14
Running mode when frequency
reference lower than frequency
lower limit
0: Run at frequency reference lower limit
1: Stop
2: Run at zero speed
0 0xF80E/0x080E
F8-16
Accumulative power-on time
threshold
0 to 65000 h 0h 0xF810/0x0810
F8-17
Accumulative running time
threshold
0 to 65000 h 0h 0xF811/0x0811
F8-18 Startup protection selection
0: Disabled
1: Enabled
0 0xF812/0x0812
F8-19 Frequency detection value 1 0.00 Hz to max. frequency 50.00 Hz 0xF813/0x0813
F8-20 Frequency detection hysteresis 1 0.0% to 100.0% 5.0% 0xF814/0x0814
F8-21
Detection width of target
frequency reached
0.0% to 100.0% 0.0% 0xF815/0x0815
F8-25
Switchover frequency of accel.
time 1 and accel. time 2
0.00 Hz to maximum frequency 0.00 Hz 0xF819/0x0819
F8-26
Switchover frequency of decel.
time 1 and decel. time 2
0.00 Hz to maximum frequency 0.00 Hz 0xF81A/0x081A
F8-27
Set highest priority to terminal
JOG function
0: Disabled
1: Enabled
0 0xF81B/0x081B
F8-30 Detection of frequency1 0.00 Hz to max. frequency 50.00 Hz 0xF81E/0x081E
F8-31 Detection width of frequency1 0.0% to 100.0% (max. frequency) 0.0% 0xF81F/0x081F
F8-34 Zero current detection level 0.0% to 300.0% (rated motor current) 5.0% 0xF822/0x0822
F8-35 Zero current detection delay 0.01s to 600.00s 0.10s 0xF823/0x0823
F8-36 Output overcurrent threshold
0.0% (no detection)
0.1% to 300.0% (rated motor current)
200.0% 0xF824/0x0824
F8-37
Output overcurrent detection
delay
0.00s to 600.00s 0.00s 0xF825/0x0825
F8-38 Detection level of current1 0.0% to 300.0% (rated motor current) 100.0% 0xF826/0x0826
F8-39 Detection width of current1 0.0% to 300.0% (rated motor current) 0.0% 0xF827/0x0827
F8-42 Timing function
0: Disabled
1: Enabled
0 0xF82A/0x082A
F8-43 Running time setting channel
0: Set by F8-44
1: AI
0 0xF82B/0x082B
F8-44 Running time 0.0 to 6500.0 min 0.0 min 0xF82C/0x082C
F8-45 AI input voltage lower limit 0.00 V to F8-46 3.10 V 0xF82D/0x082D
F8-46 AI input voltage upper limit F8-45 to 10.00 V 6.80 V 0xF82E/0x082E
F8-48 Cooling fan working mode
0: Working during drive running
1: Working continuously
2: Working when temperature reached
0 0xF830/0x0830
F8-49 Wakeup frequency F8-51 to max. frequency (F0-10) 0.00 Hz 0xF831/0x0831
F8-50 Wakeup delay time 0.0 to 6500.0s 0.0s 0xF832/0x0832
F8-51 Hibernating frequency 0.00 Hz to wakeup frequency (F8-49) 0.00 Hz 0xF833/0x0833
F8-52 Hibernating delay time 0.0 to 6500.0 s 0.0s 0xF834/0x0834
F8-53 Running time threshold this time 0.0 to 6500.0 min 0.0 min 0xF835/0x0835