5 Parameter Table
- 41 -
Para. No. Para. Name Setting Range Default Comms. Address
F9-14 1st fault type 0: No fault
1: Reserved
2: Overcurrent during acceleration
3: Overcurrent during deceleration
4: Overcurrent at constant speed
5: Overvoltage during acceleration
6: Overvoltage during deceleration
7: Overvoltage at constant speed
8: Pre-charge resistor overloaded
9: Undervoltage
10: AC drive overloaded
11: Motor overloaded
12: Input phase loss
13: Output phase loss
14: IGBT overheat
15: External fault
16: Communication abnormal
17: Reserved
18: Current detection abnormal
19: Motor auto-tuning abnormal
20: Reserved
21: Parameter read-write abnormal
22: Reserved
23: Motor short circuited to ground
24: Reserved
25: Reserved
26: Accumulative running time reached
29: Accumulative power-on time reached
30: Load lost
31: PID feedback lost during running
40: Overcurrent fast prevention timeout
41: Reserved
42: Excessive speed deviation
43: Reserved
45: Reserved
51: Reserved
55: Slave fault in speed synchronous
- 0xF90E/0x090E
F9-15 2nd fault type - 0xF90F/0x090F
F9-16 3rd (latest) fault type - 0xF910/0x0910
F9-17 Frequency upon 3rd fault - - 0xF911/0x0911
F9-18 Current upon 3rd fault - - 0xF912/0x0912
F9-19 Bus voltage upon 3rd fault - - 0xF913/0x0913
F9-20 DI state upon 3rd fault - - 0xF914/0x0914
F9-21 DO state upon 3rd fault - - 0xF915/0x0915
F9-22 AC drive state upon 3rd fault - - 0xF916/0x0916
F9-23 Power-on time upon 3rdfault - - 0xF917/0x0917
F9-24 Running time upon 3rd fault - - 0xF918/0x0918
F9-27 Frequency upon 2nd fault - - 0xF91B/0x081B
F9-28 Current upon 2nd fault - - 0xF91C/0x091C
F9-29 Bus voltage upon 2nd fault - - 0xF91D/0x091D
F9-30 DI state upon 2nd fault - - 0xF91E/0x091E
F9-31 DO state upon 2nd fault - - 0xF91F/0x091F