5 Parameter Table
- 42 -
Para. No. Para. Name Setting Range Default Comms. Address
F9-32 AC drive state upon 2nd fault - - 0xF920/0x0920
F9-33 Power-on time upon 2nd fault - - 0xF921/0x0921
F9-34 Running time upon 2nd fault - - 0xF922/0x0922
F9-37 Frequency upon 1st fault - - 0xF925/0x0925
F9-38 Current upon 1st fault - - 0xF926/0x0926
F9-39 Bus voltage upon1st fault - - 0xF927/0x0927
F9-40 DI state upon 1st fault - - 0xF928/0x0928
F9-41 DO state upon 1st fault - - 0xF929/0x0929
F9-42 AC drive state upon 1st fault - - 0xF92A/0x092A
F9-43 Power-on time upon 1st fault - - 0xF92B/0x092B
F9-44 Running time upon 1st fault - - 0xF92C/0x092C
F9-47 Fault protection action selection 1 00000 to 22222 00000 0xF92F/0x092F
F9-48 Fault protection action selection 2 00000 to 11111 00000 0xF930/0x0930
F9-49 Fault protection action selection 3 00000 to 22222 00000 0xF931/0x0931
F9-54
Frequency selection for
continuing to run upon fault
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality
0 0xF936/0x0936
F9-55 Backup frequency upon fault 0.0% to 100.0% (maximum frequency) 100.0% 0xF937/0x0937
F9-59
Power dip ride-through function
selection
0: Disabled
1: Bus voltage constant control
2: Decelerate to stop
0 0xF93B/0x093B
F9-60
Threshold of power dip ride-
through function disabled
80% to 100% (standard bus voltage) 85% 0xF93C/0x093C
F9-61
Judging time of bus voltage
recovering from power dip
0.0 to 100.0 s 0.5s 0xF93D/0x093D
F9-62
Threshold of power dip ride-
through function enabled
60% to 100% 80% 0xF93E/0x093E
F9-63 Load lost protection
0: Disabled
1: Enabled
0 0xF93F/0x093F
F9-64 Load lost detection level 0.0% to 100.0% 10.0% 0xF940/0x0940
F9-65 Load lost detection time 0.0 to 60.0s 1.0s 0xF941/0x0941
F9-71 Power dip ride-through gain Kp 0 to 100 40 0xF947/0x0947
F9-72
Power dip ride-through integral
coefcient
0 to 100 30 0xF948/0x0948
F9-73
Deceleration time of power dip
ride-through
0.0 to 300.0s 20.0s 0xF949/0x0949
F9-74 Restart mode after fault reset
0: Normal
1: Catching a spinning motor
0 0xF94A/0x094A
Group FA: PID Function
FA-00 PID reference setting channel
0: Set by FA-01
1: AI
2: External operating panel potentiometer
4: Pulse reference (DI4)
5: Via communication
6: Multi-reference
0 0xFA00/0x0A00