5 Parameter Table
- 44 -
Para. No. Para. Name Setting Range Default Comms. Address
FA-25 PID integral property
00 to 11
Whether to stop integral
operation when PID output
reaches the limit
0: Continue integral operation
1: Stop integral operation
Integral separation
0: Disabled
1: Enabled
00 0xFA19/0x0A19
FA-26
Detection level of PID feedback
loss
0%: No detection
0.1% to 100.0%
0.0% 0xFA1A/0x0A1A
FA-27
Detection time of PID feedback
loss
0.0 to 20.0s 0.0s 0xFA1B/0x0A1B
FA-28 Selection of PID operation at stop
0: Disabled
1: Enabled
0 0xFA1C/0x0A1C
Group Fb: Wobble Function, Fixed Length and Count
Fb-00 Wobble setting mode
0: Relative to the frequency reference
1: Relative to the max. frequency
0 0xFB00/0x0B00
Fb-01 Wobble amplitude 0.0% to 100.0% 0.0% 0xFB01/0x0B01
Fb-02 Wobble step 0.0% to 50.0% 0.0% 0xFB02/0x0B02
Fb-03 Wobble cycle 0.1 to 3000.0s 10.0s 0xFB03/0x0B03
Fb-04
Triangular wave rising time
coefcient
0.1% to 100.0% 50.0% 0xFB04/0x0B04
Fb-05 Set length 0 to 65535 m 1000 m 0xFB05/0x0B05
Fb-06 Actual length 0 to 65535 m 0 m 0xFB06/0x0B06
Fb-07 Number of pulses per meter 0.1 to 6553.5 100.0 0xFB07/0x0B07
Fb-08 Set count value 1 to 65535 1000 0xFB08/0x0B08
Group FC: Multi-Reference and Simple PLC Function
FC-00 Reference0 -100.0% to 100.0% 0.0% 0xFC00/0x0C00
FC-01 Reference1 -100.0% to 100.0% 0.0% 0xFC01/0x0C01
FC-02 Reference2 -100.0% to 100.0% 0.0% 0xFC02/0x0C02
FC-03 Reference3 -100.0% to 100.0% 0.0% 0xFC03/0x0C03
FC-04 Reference4 -100.0% to 100.0% 0.0% 0xFC04/0x0C04
FC-05 Reference5 -100.0% to 100.0% 0.0% 0xFC05/0x0C05
FC-06 Reference6 -100.0% to 100.0% 0.0% 0xFC06/0x0C06
FC-07 Reference7 -100.0% to 100.0% 0.0% 0xFC07/0x0C07
FC-16 Simple PLC running mode
0: Stop after running one cycle
1: Keep nal values after running one cycle
2: Repeat after running one cycle
0 0xFC10/0x0C10