EasyManua.ls Logo

Inovance MD290T45G/55P - Page 115

Inovance MD290T45G/55P
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Description of Parameters
- 114 -
6
)WR)DQG)WR)GH¿QH$,FXUYHDQG$,FXUYHUHVSHFWLYHO\$,FXUYH
2 and AI curve 3 have the same function and usage as AI curve 1 does. Refer to
S
t
e
p
1
:
S
e
t
A
I
c
u
r
v
e
.
Figure 6-14 Set AI curve 2
AI
Corresponding
percentage
80.
20.
0.00
2.
00
10.
00
F4-18
0.0
F4-20
F4-19
F4-21
0%
0%
V/mA V/mA
Function Code Parameter Name Setting Range Default
F4-18
AI curve 2 min. input 0.00 V to F4-20 0.00 V
F4-19
Corresponding percentage of
AI curve 2 min. input
-100.00% to 100.0% 0.0%
F4-20
AI2 curve max. input F4-18 to 10.00 V 10.00 V
F4-21
Corresponding percentage of
AI curve 2 max. input
-100.00% to 100.0% 100.0%
F4-23
AI curve 3 min. input 0.00 V to F4-25 0.00 V
F4-24
Corresponding percentage of
AI curve 3 min. input
-100.00% to 100.0% 0.0%
F4-25
AI curve 3 max. input F4-23 to 10.00 V 10.00 V
F4-26
Corresponding percentage of
AI curve 3 max. input
-100.00% to 100.0% 100.0%

Table of Contents

Related product manuals