6. Description of Parameters
- 174 -
6
Function Code Parameter Name Setting Range Default
A7-01
AC drive output
terminal control
source selection
Relay (T/A-T/B-T/C):
0: AC drive control
1: User programmable card control
FMR (FM used as digital output):
0: AC drive control
1: User programmable card control
DO1:
0: AC drive control
1: User programmable card control
AO1:
0: AC drive control
1: User programmable card control
FMP (FM used as pulse output):
0: AC drive control
1: User programmable card control
00000
A7-03
PLC program controls
the FMP output
0.0% to 100.0% 0.0%
A7-04
PLC program controls
the AO1 output
0.0% to 100.0% 0.0%
A7-05
Selection of PLC
program controlling
digital output
Relay1
0: Disabled
1: Enabled
FMR
0: Disabled
1: Enabled
DO
0: Disabled
1: Enabled
000
The base value of A7-03 is F5-09 (Max. FMP output frequency). The base value of
A7-04 is 10 V (voltage output) or 20 mA (current output).

Table of Contents