6. Description of Parameters
- 175 -
6
1. Set running command
When F0-02 = 2 (the command source is communication) and A7-00 = 1 (the user
programmable card is enabled), drive running is controlled by setting of A7-08.
You can implement control of the AC drive via PLC program by operating
corresponding D component.
Function Code Parameter Name Setting Range Default
A7-08
Setting running command
via the user programmable
card
0 to 7
0: No command
1: Forward run
2: Reverse run
3: Forward jog
4:Reverse jog
5: Coast to stop
6: Decelerate to stop
7: Fault reset
0
2. Set frequency reference
When frequency reference setting channel is communication and A7-00 = 1 (user
programmable card is enabled), frequency reference of the AC drive is determined by
setting of A7-06.
You can implement control of frequency reference of AC drive via PLC program by
operating corresponding D component.
Function Code Parameter Name Setting Range Default
A7-06
Setting frequency reference
via the user programmable
card
-100.00% to 100.00% 0.00%
The base value of this parameter is F0-10 (Max. frequency).
3. 6HWXVHUGH¿QHGIDXOWV
:KHQ$ XVHUSURJUDPPDEOHFDUGLVHQDEOHG\RXFDQVHWXVHUGH¿QHGIDXOWV
Err80 to Err89 by operating corresponding D component to change setting of A7-09 in
the range of 80 to 89.
Function Code Parameter Name Setting Range Default
A7-09
Setting torque reference via
the user programmable card
0: No fault
WR8VHUGH¿QHG
fault code
0
If setting of A7-09 is out of 80 to 89, the setting will not take effect.