6. Description of Parameters    
- 191 -
6
Function Code Parameter Name Setting Range Default
F5-09
Max. FMP output frequency 0.01 to 100.00 kHz 50.00 kHz
This function parameter sets maximum pulse output frequency when FM terminal is used for 
pulse output.
Function Code Parameter Name Setting Range Default
F5-10
$2]HURRIIVHWFRHI¿FLHQW -100.0% to 100.0% 0.0%
F5-11
AO1 gain -10.00 to 10.00 1.00
F5-12
$2]HURRIIVHWFRHI¿FLHQW -100.0% to 100.0% 0.00%
F5-13
AO2 gain -10.00 to 10.00 1.00
These four function parameters generally correct zero offset of analog output and output 
DPSOLWXGHHUURU7KH\FDQDOVRGH¿QHUHTXLUHG$2FXUYH
=HURRIIVHWFRHI¿FLHQWRI$2DQG$2FRUUHVSRQGVWR9RUP$<RXFDQFDOFXODWH
WKHJDLQDQGWKH]HURRIIVHWFRHI¿FLHQWIURPWKHIROORZLQJIRUPXODV
K 
=
(Y1  Y2) x Xmax
(X1  X2) x Ymax
 
b =
(X1 xY2  X2 x Y1)
(X1  X2) x Ymax
 
In the formulas:
 
Ɣ
"b" represents zero offset.
 
Ɣ
"k" represents gain.
 
Ɣ
"X" represents output frequency.
 
Ɣ
"Y" represents actual output of the AO.
 
Ɣ
" Xmax " represents max. output frequency (determined by F0-10).
 Ɣ "Ymax" represents max. output 10 V or 20 mA.
For example, AO is used for output of frequency reference. To implement output of 8 V (Y1) at 0 
Hz (x1) and output of 4 V (Y2) at 40 Hz (X2) according to the formulas, you can obtain gain and 
]HURRIIVHWFRHI¿FLHQWDVIROORZV
K =
(8  4) x 50
(0  40) x 10
 = 
0.5
 
b =
(0 x 4 - 40 x 8)
(0 - 40) x 10
= 80%
Then you can set F5-11 to -0.5 and set F5-10 to 80%.
AO output signal type and corresponding max. value are as follows:
AO1 output signal Corresponding Max. Output (Ymax)
Voltage  10 V
Current 20 mA