Appendix
- 315 -
12
Para. No. Para. Name Setting Range Default Property Page
Group F5: Output Terminals
F5-00 FM terminal output mode 0: Pulse output (FMP)
1: Digital output (FMR)
0
ƿ
1
8
2
F5-01 FMR function selection 0: No output
1: AC drive running
2: Fault output
3: Frequency level detection 1
4: Frequency reached
5: Zero-speed running (no output
at stop)
6: Motor overload pending
7: AC drive overload pending
8: Set count value reached
9: Designated count value reached
10: Length reached
11: PLC cycle completed
12: Accumulative running time
reached
13: Frequency limited
15: Ready for RUN
16: AI1 > AI2
17: Frequency upper limit reached
18: Frequency lower limit reached
(no output at stop)
19: Undervoltage
20: Communication setting
21: Reserved
22: Reserved
23: Zero-speed running 2 (having
output at stop)
24: Accumulative power-on time
reached
25: Frequency level detection 2
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing reached
31: AI1 input exceeding limit
32: Load lost
33: Reverse running
34: Zero current
35: IGBT temperature reached
36: Output current exceeding limit
37: Frequency lower limit reached
(having output at stop)
38: Alarm output
39: Motor overheat pending
40: Current running time reached
41: Fault output
0
ƿ
1
8
2
F5-02 Relay (T/A-T/B-T/C) function
selection
2
ƿ
1
8
2
F5-03 Extension card relay (P/A-P/
B-P/C) function selection
0
ƿ
1
8
2
F5-04 DO1 function selection 1
ƿ
1
8
2
F5-05 Extension card DO2 function
selection
4
ƿ
1
8
2
F5-06 FMP function selection 0
ƿ
1
9
0
F5-07 AO1 function selection 0
ƿ
1
9
0
F5-08 AO2 function selection 1
ƿ
1
9
0