Appendix
- 316 -
12
Para. No. Para. Name Setting Range Default Property Page
F5-09 Max. FMP output frequency 0.01 to 100.00 kHz 50.00 kHz
ƿ
1
9
1
F5-10 $2]HURRIIVHWFRHI¿FLHQW -100.0% to 100.0% 0.0%
ƿ
1
9
1
F5-11 AO1 gain -10.00 to 10.00 1.00
ƿ
1
9
1
F5-12 $2]HURRIIVHWFRHI¿FLHQW -100.0% to 100.0% 0.00%
ƿ
1
9
1
F5-13 AO2 gain -10.00 to 10.00 1.00
ƿ
1
9
1
F5-17 FMR output delay
0.0s to 3600.0s
0.0s
ƿ
1
8
5
F5-18 Relay 1 output delay
0.0s to 3600.0s
0.0s
ƿ
1
8
5
F5-19 Relay 2 output delay
0.0s to 3600.0s
0.0s
ƿ
1
8
5
F5-20 DO1 output delay
0.0s to 3600.0s
0.0s
ƿ
1
8
5
F5-21 DO2 output delay
0.0s to 3600.0s
0.0s
ƿ
1
8
5
F5-22 DO active mode selection 1 00000 to 11111
Relay1 active mode:
0: Positive logic active
1: Negative logic active
FMR active mode:
0: Positive logic active
1: Negative logic active
Relay2 active mode:
0: Positive logic active
1: Negative logic active
DO2 active mode:
0: Positive logic active
1: Negative logic active
DO1 active mode:
0: Positive logic active
1: Negative logic active
00000
ƿ
1
8
5
Group F6: Start/Stop Control
F6-00 Start mode 0: Direct start
1: Catching a spinning motor
2: Pre-excited start
3: SVC quick start
0
ƿ
1
3
6
F6-01 Mode of catching a spinning
motor
0: From stop frequency
1: From zero speed
2: From max. frequency
0
ƾ
1
3
6
F6-02 Speed of catching a spinning
motor
1 to 100 20
ƿ
1
3
6
F6-03 Start frequency 0.00 to 10.00 Hz 0.00 Hz
ƿ
1
3
6
F6-04 Start frequency holding time 0.0s to 100.0s 0.0s
ƾ
1
3
6
F6-05 DC injection braking 1 level/
Pre-excitation level
0% to 100% 50%
ƾ
1
3
6
F6-06 DC injection braking 1 active
time /Pre-excitation active time
0.0s to 100.0s 0.0s
ƾ
1
3
6
F6-07 Acceleration/Deceleration mode 0 to 2 0
ƾ
1
4
2
F6-08 Time proportion of S-curve start
segment
0.0% to (100.0% – F6-09) 30.0%
ƾ
1
4
2
F6-09 Time proportion of S-curve end
segment
0.0% to (100.0% – F6-08) 30.0%
ƾ
1
4
2

Table of Contents