Appendix
- 333 -
12
Para. No. Para. Name Setting Range Default Property Page
A1-05 VDI active state setting mode 00000 to 11111
VDI2:
0: Decided by state of VDOx
1: Decided by A1-06
VDI1:
0: Decided by state of VDOx
1: Decided by A1-06
VDI3:
0: Decided by state of VDOx
1: Decided by A1-06
VDI5:
0: Decided by state of VDOx
1: Decided by A1-06
VDI4:
0: Decided by state of VDOx
1: Decided by A1-06
00000
ƾ
1
8
6
A1-06 Selection of VDI active state 00000 to 11111
VDI2:
0: Inactive
1: Active
VDI1:
0: Inactive
1: Active
VDI3:
0: Inactive
1: Active
VDI5:
0: Inactive
1: Active
VDI4:
0: Inactive
1: Active
00000
ƾ
1
8
6
A1-07 Function selection for AI1 used as
DI
0: No function
1: Forward run (FWD)
2: Reverser run (REV)
3: Three-wire control
4: Forward jog (FJOG)
5: Reverse jog (RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset (RESET)
10: RUN disabled
11: External fault normally-open
input
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
16: Terminal 1 for acceleration/
deceleration time selection
17: Terminal 2 for acceleration/
deceleration time selection
18: Frequency reference setting
channel switchover
19: UP and DOWN setting clear
(terminal, operation panel)
0
ƾ
1
8
9