46
F6-07 Run reverse control
Default 0
0 Run reverse enabled Setting
range
1 Run reverse disabled
0: Reverse is permitted.
1: Reverse is forbidden.
F6-08 FWD/REV dead zone time
Default 0.00.0s
Setting range 0.00s ~ 3000.0s
It is the interval at the zero output frequency when the motor changes rotation direction, shown in
Fig. 6-6:
Output frequency
Forward rotation
Run time
Dead zone time
Reverse rotation
Output frequency
Forward rotation
Run time
Dead zone time
Reverse rotation
Fig 6-1 FWD/REV dead zone time
F6-09 Restart terminal enable selection
Default 0
0 Enabled Setting
range
1 Disabled
This function code is used to enhance the security of the system.
If it is set as “0”, it has two functions:
First, if the running command exists when the inverter is
powered on, it must delete the running command to exit the running protection status.
Second, if
the running command still exists when the inverter implements fault reset, it must delete the running
command to exit the running protection status. This function can prevent the danger resulting from
the unexpected running of the inverter.
F6-10 Preset frequency arrived checkout value
Default 0.00Hz
Setting range 0.00 Hz ~ maximum frequency