When the output frequency of the inverter reaches the setting frequency value, this function can
adjust the detection amplitude value, as shown in the figure below:
Output frequency
Detection amplitude value
Frequency detection signals
DO1 and RELAY1
Tim e
Tim e
Output frequency
Detection amplitude value
Frequency detection signals
DO1 and RELAY1
Tim e
Tim e
Fig. 6-2 Frequency Reaching Checkout Amplitude Value
F6-11 Reserved
Default 0
F6-12 STOP/RESET function
Default 0
0 The STOP function is invalid under the terminal control. Setting
range
1 The STOP function is valid under the terminal control.
The RESET function is valid under any status.
F6-13
Reserved Default 0
Multi-speed 0
Default 0
0 Multi-speed 0 is the value of F0-04
1 Multi-speed 0 depends on PULSE value
2 Multi-speed 0 depends on panel potentiometer
F6-14
Setting
range
3 Multi-speed 0 depends on AI
F6-15 Multi-speed 1
Default 20.0Hz
Setting range 0 Hz ~ maximum frequency
F6-16 Multi-speed 2
Default 40.0Hz
Setting range 0 Hz ~ maximum frequency
F6-17 Multi-speed 3
Default 50.0Hz