EasyManua.ls Logo

Inovance MD310 T1.5B - Group F1: Motor 1 Parameters

Inovance MD310 T1.5B
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Parameter Table
- 28 -
Para� No� Para� Name Setting Range Unit Default Commission
F0-23 Retentive of digital
setting frequency upon
stop
0: Not retentive
1: Retentive
N�A� 0
F0-24 Motor parameter group
selection
0: Motor parameter group 1
1: Motor parameter group 2
N�A� 0
F0-25 Acceleration/
Deceleration time base
frequency
0: Max� frequency (F0-10)
1: Frequency reference
2: 100
Hz 0
F0-26 Base frequency for UP/
DOWN modication
during running
0: Running frequency
1: Frequency reference
N�A� 0
F0-27 Binding command
source to frequency
source
0000 to 9999 N�A� 0000
Group F1: Motor 1 Parameters
Para� No� Para� Name Setting Range Unit Default Commission
F1-00 Motor type selection 0: Common asynchronous motor
1: Variable frequency asynchronous motor
N�A� 0
F1-01 Rated motor power 0�1 to 30�0 kW Model
dependent
F1-02 Rated motor voltage 1 to 1000 V Model
dependent
F1-03 Rated motor current 0�01 to 655�35 A Model
dependent
F1-04 Rated motor frequency 0�01 to max frequency Hz Model
dependent
F1-05 Rated motor speed 1 to 65535 RPM Model
dependent
F1-06 Stator resistance
(asynchronous motor)
0�001 to 65�535 Model
dependent
F1-07 Rotor resistance 0�001 to 65�535 Model
dependent
F1-08 Leakage inductive
reactance
0�01 to 655�35 mH Model
dependent
F1-09 Mutual inductive
reactance
0�1 to 6553�5 mH Model
dependent
F1-10 No-load current
(asynchronous motor)
0�01 to F1-03 A Model
dependent
F1-37 Auto-tuning selection 0: No auto-tuning
1: Static auto-tuning 1
2: Complete dynamic auto-tuning
3: Static auto-tuning 2
N�A� 0

Table of Contents

Related product manuals