6. Description of Parameters
- 168 -
● Flexible connection
For the master in speed control, perform the following settings. Note that only the
setting of F8-15 can be modied.
Function Code Parameter Name Setting Range Setting
Fd-00
Baud rate 0000 to 6039 Keep thousands position of
this parameter to the same
value for the master and
slave.
A8-00
Selection of
point-point
communication
0: Disabled
1: Enabled
1
A8-01
Master and slave
selection
0: Master
1: Slave
0
F0-10
Max. frequency 5.00 to 500.00 Hz 50.00 Hz
Keep the same setting of
this parameter for the master
and slave.
F8-15
Droop rate 0.00 to 10.00 Hz 1.00 Hz
F0-17
Acceleration time 1 0.0 to 6500.0s Keep the same setting of
this parameter for the master
and slave.
F0-18
Deceleration time 1 0.0 to 6500.0s Keep the same setting of
this parameter for the master
and slave.
For slave in speed control, perform the following settings. Note that only setting of F8-
15 can be modied.
Function Code Parameter Name Setting Range Setting
Fd-00
Baud rate 0000 to 6039 Keep thousands
position of this
parameter to the
same value for the
master and slave.
A8-00
Selection of
point-point
communication
0: Disabled
1: Enabled
1
A8-01
Master and slave
selection
0: Master
1: Slave
1