Commissioning and Trial Run
‑39‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F4‑00 62464 DI1 hardware source 0: No selection
1: Power supply unit DI1
2: Power supply unit DI2
3: Power supply unit DI3
4: Power supply unit DI4
5: Power supply unit DIO1
6: Power supply unit DIO2
7: Power supply unit DIO3
8: Power supply unit DIO4
101: Expansion card 1 DI1
102: Expansion card 1 DI2
103: Expansion card 1 DI3
104: Expansion card 1 DI4
105: Expansion card 1 DI5
106: Expansion card 1 DI6
107: Expansion card 1 DI7
108: Expansion card 1 DI8
201: Expansion card 2 DI1
202: Expansion card 2 DI2
203: Expansion card 2 DI3
204: Expansion card 2 DI4
205: Expansion card 2 DI5
206: Expansion card 2 DI6
207: Expansion card 2 DI7
208: Expansion card 2 DI8
0 Modifiable
only at stop
F4‑01 62465 DI1 function selection 0: No function
1: Running enable
2: Incoming breaker
feedback
3: Auxiliary breaker
feedback
4: Residual current device
(RCD) feedback
5: Fault reset
6: Drive unit running
prohibition
7: Drive unit coast to stop
8: Drive unit stops
according to preset mode
0 Modifiable
only at stop
F4‑02 62466 DI2 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑03 62467 DI2 function selection Same as F4‑01 0 Modifiable
only at stop
F4‑04 62468 DI3 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑05 62469 DI3 function selection Same as F4‑01 0 Modifiable
in any states