Commissioning and Trial Run
‑40‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F4‑06 62470 DI4 hardware source Same as F4‑00 0 ‑ Modifiable
only at stop
F4‑07 62471 DI4 function selection Same as F4‑01 0 ‑ Modifiable
only at stop
F4‑08 62472 DI5 hardware source Same as F4‑00 0 ‑ Modifiable
only at stop
F4‑09 62473 DI5 function selection Same as F4‑01 0 ‑ Modifiable
only at stop
F4‑10 62474 DI6 hardware source Same as F4‑00 0 ‑ Modifiable
only at stop
F4‑11 62475 DI6 function selection Same as F4‑01 5 ‑ Modifiable
only at stop
F4‑12 62476 DI7 hardware source Same as F4‑00 0 ‑ Modifiable
only at stop
F4‑13 62477 DI7 function selection Same as F4‑01 0 ‑ Modifiable
only at stop
F4‑14 62478 DI8 hardware source Same as F4‑00 0 ‑ Modifiable
only at stop
F4‑15 62479 DI8 function selection Same as F4‑01 0 ‑ Modifiable
only at stop
F4‑16 62480 DI1 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑17 62481 DI2 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑18 62482 DI3 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑19 62483 DI4 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑20 62484 DI5 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑21 62485 DI6 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑22 62486 DI7 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑23 62487 DI8 active delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑24 62488 DI1 inactive delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑25 62489 DI2 inactive delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑26 62490 DI3 inactive delay 0.00s to 600.00s 0.00 s Modifiable
in any states
F4‑27 62491 DI4 inactive delay 0.00s to 600.00s 0.00 s Modifiable
in any states