Commissioning and Trial Run
‑49‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
FD‑12 64780 CAN baud rate 0: 20 Kbps
1: 50 Kbps
2: 100 Kbps
3: 125 Kbps
4: 250 Kbps
5: 500 Kbps
6: 1 Mbps
5 ‑ Modifiable
in any states
FD‑13 64781 CAN station No. 1–127 16 ‑ Modification
prohibited
FD‑14 64782 Received CAN frames
per unit of time (real‑
time)
0–65535 0 ‑ Modification
prohibited
FD‑15 64783 Maximum value of
node receive error
counter (real‑time)
0–65535 0 ‑ Modification
prohibited
FD‑16 64784 Maximum value of
node transmit error
counter (real‑time)
0–65535 0 ‑ Modification
prohibited
FD‑17 64785 Bus disconnection
times per unit of time
0–65535 0 ‑ Modification
prohibited
FD‑18 64786 Power supply unit No. 1–15 1 ‑ Modifiable
in any states
FD‑19 64787 CAN communication
interruption
coefficient
1–15 1 ‑ Modifiable
in any states
FD‑34 64802 CANopen mode 0: Standard mode
1: Expert mode
0 ‑ Modifiable
in any states
FD‑35 64803 CANopen disable time 0–65535 0 ‑ Modifiable
in any states
FD‑36 64804 CANopen event time 0–65535 0 ‑ Modifiable
in any states
FD‑39 64807 AC drive station
number setting
function
0: Disabled
1: Enabled
0 ‑ Modifiable
in any states
FD‑40 64808 Power supply unit
station number set
manually
0–127 0 ‑ Modifiable
in any states
FD‑41 64809 Drive unit 1 station
number set manually
0–127 0 ‑ Modifiable
in any states
FD‑42 64810 Drive unit 2 station
number set manually
0–127 0 ‑ Modifiable
in any states
FD‑43 64811 Drive unit 3 station
number set manually
0–127 0 ‑ Modifiable
in any states
FD‑44 64812 Drive unit 4 station
number set manually
0–127 0 ‑ Modifiable
in any states