Commissioning and Trial Run
48
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
FD‑00 64768 RS485 baud rate 0: 300 bps
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps
6: 19200 bps
7:38400 bps
8: 57600 bps
9: 115200 bps
5 Modifiable
only at stop
FD‑01 64769 RS485 data format 0: No check (8‑N‑2)
1: Even parity check (8‑E‑1)
2: Odd parity check (8‑O‑1)
3: No check (8‑N‑1)
4: No check (7‑N‑2)
5: Even parity check (7‑E‑1)
6: Odd parity check (7‑O‑1)
7: No check (7‑N‑1)
0 Modifiable
in any states
FD‑02 64770 RS485 local address 1127 16 Modification
prohibited
FD‑03 64771 RS485 response delay 020 ms 2 ms Modifiable
in any states
FD‑04 64772 RS485
communication
timeout
0.0s to 60.0s 0.0 s Modifiable
in any states
FD‑06 64774 Communication fault
auto reset
0: Disabled
1: Enabled
1 Modifiable
in any states
FD‑07 64775 Maximum station
number automatically
assigned
08 0 Modifiable
in any states
FD‑09 64777 CANopen/CANlink
communication state
Ones (CANopen)
0: Stop
1: Initialized
2: Pre‑running
8: Running
Tens (CANlink)
0: Stop
1: Initialized
2: Pre‑running
8: Running
0 Modification
prohibited
FD‑10 64778 Communication
protocol
1: CANopen
2: CANlink
3: Communication card
mode
1 Modifiable
in any states