Commissioning and Trial Run
‑55‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
A2‑11 41483 AI2 input selection 0: Voltage input
1: Current input
2: PT100 input
3: PT1000 input
4: KTY84 input
5: PTC130 input
0 ‑ Modifiable
only at stop
A3‑00 41728 Filter time of
expansion card 2
terminals (DI1 to DI4)
0.000s to 5.000s 0.010 s Modifiable
in any states
A3‑01 41729 Filter time of
expansion card 2
terminals (DI5 to DI8)
0.000s to 5.000s 0.010 s Modifiable
in any states
A3‑05 41733 AI1 filter time 0.00s to 10.00s 0.10 s Modifiable
in any states
A3‑06 41734 AI2 fitter time 0.00s to 10.00s 0.10 s Modifiable
in any states
A3‑10 41738 AI1 input selection 0: Voltage input
1: Current input
2: PT100 input
3: PT1000 input
4: KTY84 input
5: PTC130 input
0 ‑ Modifiable
only at stop
A3‑11 41739 AI2 input selection 0: Voltage input
1: Current input
2: PT100 input
3: PT1000 input
4: KTY84 input
5: PTC130 input
0 ‑ Modifiable
only at stop
AC‑00 44032 Power supply unit ‑
AI1 measured voltage
1
0.000–12.000 V 2.000 V Modifiable
in any states
AC‑01 44033 Power supply unit ‑
AI1 displayed voltage
1
0.000–12.000 V 2.000 V Modifiable
in any states
AC‑02 44034 Power supply unit ‑
AI1 measured voltage
2
0.000–12.000 V 2.000 V Modifiable
in any states
AC‑03 44035 Power supply unit ‑
AI1 displayed voltage
2
0.000–12.000 V 2.000 V Modifiable
in any states
AC‑04 44036 Power supply unit ‑
AI2 measured voltage
1
0.000–12.000 V 2.000 V Modifiable
in any states
AC‑05 44037 Power supply unit ‑
AI2 displayed voltage
1
0.000–12.000 V 2.000 V Modifiable
in any states