Commissioning and Trial Run
‑76‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F3‑00 62208 V/f curve setting 0: Linear V/f
1: Multi‑point V/f
2: Square V/f
3: 1.2‑power V/f
4: 1.4‑power V/f
6: 1.6‑power V/f
8: 1.8‑power V/f
10: V/f complete
separation
11: V/f half separation
0 ‑ Modifiable
only at stop
F3‑01 62209 Torque boost 0.0% to 30.0% Model
dependent
% Modifiable
in any states
F3‑02 62210 Cutoff frequency of
torque boost
0.00–655.35 Hz 50.00 Hz Modifiable
only at stop
F3‑03 62211 Multi‑point V/f
frequency 1
0.00–655.35 Hz 0.00 Hz Modifiable
only at stop
F3‑04 62212 Multi‑point V/f voltage
1
0.0% to 100.0% 0.0 % Modifiable
only at stop
F3‑05 62213 Multi‑point V/f
frequency 2
0.00–655.35 Hz 0.00 Hz Modifiable
only at stop
F3‑06 62214 Multi‑point V/f voltage
2
0.0% to 100.0% 0.0 % Modifiable
only at stop
F3‑07 62215 Multi‑point V/f
frequency 3
0.00–655.35 Hz 0.00 Hz Modifiable
only at stop
F3‑08 62216 Multi‑point V/f voltage
3
0.0% to 100.0% 0.0 % Modifiable
only at stop
F3‑09 62217 V/f slip compensation
gain
0.0% to 200.0% 0.0 % Modifiable
in any states
F3‑10 62218 V/f over‑excitation
gain
0–200 64 ‑ Modifiable
in any states
F3‑11 62219 V/f oscillation
suppression gain
0–100 Model
dependent
‑ Modifiable
in any states
F3‑12 62220 Oscillation
suppression gain
function
0: Disabled
3: Enabled
3 ‑ Modifiable
only at stop
F3‑13 62221 Voltage source for V/f
separation
0: Digital setting (F3‑14)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Multi‑reference
6: Simple PLC
7: PID
8: Communication setting
0 ‑ Modifiable
in any states
F3‑14 62222 Voltage digital setting
for V/f separation
0–65535 V 0 V Modifiable
in any states