Commissioning and Trial Run
‑77‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F3‑15 62223 Voltage rise time of V/f
separation
0.0s to 1000.0s 0.0 s Modifiable
in any states
F3‑16 62224 Voltage decline time
of V/f separation
0.0s to 1000.0s 0.0 s Modifiable
in any states
F3‑17 62225 Stop mode selection
for V/f separation
0: Frequency and voltage
decline to 0 independently
1: Frequency declines after
voltage declines to 0
0 ‑ Modifiable
only at stop
F3‑18 62226 V/f overcurret stall
prevention current
50% to 180% 150 % Modifiable
only at stop
F3‑19 62227 V/f overcurret stall
prevention
0: Disabled
1: Enabled
1 ‑ Modifiable
only at stop
F3‑20 62228 V/f overcurret stall
prevention gain
0–100 20 ‑ Modifiable
in any states
F3‑21 62229 Compensation factor
of overcurrent stall
prevention current at
high frequency
50–180 50 ‑ Modifiable
only at stop
F3‑22 62230 V/f overvoltage stall
prevention voltage
330.0–800.0 V Single‑phase
200 V: 370.0
V; Three‑
phase 400 V:
770 V
V Modifiable
only at stop
F3‑23 62231 V/f overvoltage stall
prevention
0: Disabled
1: Enabled
1 ‑ Modifiable
only at stop
F3‑24 62232 V/f overvoltage stall
prevention frequency
gain
0–100 30 ‑ Modifiable
in any states
F3‑25 62233 V/f overvoltage stall
prevention voltage
gain
0–100 30 ‑ Modifiable
in any states
F3‑26 62234 Maximum rise
frequency during
overvoltage stall
prevention
0–50 5 ‑ Modifiable
only at stop
F3‑27 62235 Slip compensation
time constant
0.1–10.0 0.5 ‑ Modifiable
in any states
F3‑28 62236 Automatic frequency
rise
0: Disabled
1: Enabled
0 ‑ Modifiable
only at stop
F3‑29 62237 Minimum motoring
torque current
10–100 50 ‑ Modifiable
only at stop
F3‑30 62238 Maximum generating
torque current
10–100 20 ‑ Modifiable
only at stop
F3‑31 62239 Automatic frequency
rise KP
0–100 50 ‑ Modifiable
in any states