EasyManua.ls Logo

Inovance MD800 Series - Page 82

Inovance MD800 Series
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Trial Run
‑81‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F4‑04 62468 DI3 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑05 62469 DI3 function selection Same as F4‑01 9 Modifiable
only at stop
F4‑06 62470 DI4 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑07 62471 DI4 function selection Same as F4‑01 14 Modifiable
only at stop
F4‑08 62472 DI5 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑09 62473 DI5 function selection Same as F4‑01 15 Modifiable
only at stop
F4‑10 62474 DI6 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑11 62475 DI6 function selection Same as F4‑01 0 Modifiable
only at stop
F4‑12 62476 DI7 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑13 62477 DI7 function selection Same as F4‑01 0 Modifiable
only at stop
F4‑14 62478 DI8 hardware source Same as F4‑00 0 Modifiable
only at stop
F4‑15 62479 DI8 function selection Same as F4‑01 0 Modifiable
only at stop
F4‑17 62481 Terminal I/O control
mode
0: Two‑wire mode 1
1: Two‑wire mode 2
2: Three‑wire mode 1
3: Three‑wire mode 2
0 Modifiable
only at stop
F4‑18 62482 Terminal UP/DOWN
change rate
0.00165.535 Hz/s 1.000 Hz/s Modifiable
in any states
F4‑19 62483 DI1 delay 0.0s to 3600.0s 0.0 s Modifiable
in any states
F4‑20 62484 DI2 delay 0.0s to 3600.0s 0.0 s Modifiable
in any states
F4‑21 62485 DI3 delay 0.0s to 3600.0s 0.0 s Modifiable
in any states

Other manuals for Inovance MD800 Series