Commissioning and Trial Run
82
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F4‑22 62486 DI active mode setting
1
Ones:
0: Active high
1: Active low
Tens:
0: Active high
1: Active low
Hundreds:
0: Active high
1: Active low
Thousands:
0: Active high
1: Active low
Ten thousands:
0: Active high
1: Active low
0 Modifiable
only at stop
F4‑23 62487 DI active mode setting
2
Ones:
0: Active high
1: Active low
Tens:
0: Active high
1: Active low
Hundreds:
0: Active high
1: Active low
Thousands:
0: Reserved
Ten thousands:
0: Reserved
0 Modifiable
only at stop
F4‑25 62489 AI1 hardware source 0: No selection
1: AI1 of power supply unit
2: AI2 of power supply unit
101: AI1 of expansion card
1
102: AI2 of expansion card
1
201: AI1 of expansion card
2
202: AI2 of expansion card
2
0 Modifiable
only at stop