Commissioning and Trial Run
‑88‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F5‑11 62731 DO2/RO2 output delay 0.0s to 3600.0s 0.0 s Modifiable
in any states
F5‑12 62732 DO3/RO3 output delay 0.0s to 3600.0s 0.0 s Modifiable
in any states
F5‑13 62733 DO4/RO4 output delay 0.0s to 3600.0s 0.0 s Modifiable
in any states
F5‑14 62734 DO5/RO5 output delay 0.0s to 3600.0s 0.0 s Modifiable
in any states
F5‑15 62735 DO/RO active mode
selection
Ones:
0: Positive logic active
1: Negative logic active
Tens:
0: Positive logic active
1: Negative logic active
Hundreds:
0: Positive logic active
1: Negative logic active
Thousands:
0: Positive logic active
1: Negative logic active
Ten thousands:
0: Positive logic active
1: Negative logic active
0 ‑ Modifiable
in any states
F6‑00 62976 Startup mode 0: Direct start
1: Flying start
(asynchronous motor)
2: Pre‑excited start
(asynchronous motor)
0 ‑ Modifiable
in any states
F6‑01 62977 Flying start mode 0: From stop frequency
1: From 50 Hz
2: From the maximum
frequency
3: Fast flying start
0 ‑ Modifiable
only at stop
F6‑02 62978 Flying start speed 1–100 20 ‑ Modifiable
in any states
F6‑03 62979 Startup frequency 0.00–10.00 kHz 0.00 Hz Modifiable
in any states
F6‑04 62980 Startup frequency
active time
0.0s to 100.0s 0.0 s Modifiable
only at stop
F6‑05 62981 Startup DC braking
current/pre‑excitation
current
0% to 100% 0 % Modifiable
only at stop
F6‑06 62982 Startup DC braking
active time/pre‑
excitation active time
0.0s to 100.0s 0.0 s Modifiable
only at stop