Commissioning and Trial Run
‑91‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F7‑03 63235 LED display running
parameter 1
Bit00: Running frequency
(Hz)
Bit01: Frequency reference
(Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI state
Bit08: DO state
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: AI3 voltage (V)
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID reference
31 ‑ Modifiable
in any states
F7‑04 63236 LED display running
parameter 2
Bit00: PID feedback
Bit01: PLC stage
Bit02: Reserved
Bit03: Running frequency 2
(Hz)
Bit04: Remaining running
time
Bit05: Reserved
Bit06: Reserved
Bit07: Reserved
Bit08: Linear speed
Bit09: Current power‑on
time (min)
Bit10: Current running
time (min)
Bit11: Reserved
Bit12: Communication
setting value
Bit13: Reserved
Bit14: Main frequency X
display
Bit15: Auxiliary frequency Y
display
0 ‑ Modifiable
in any states