92
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F7‑05 63237 LED display stop
parameters
Bit00: Frequency reference
(Hz)
Bit01: Bus voltage (V)
Bit02: DI state
Bit03: DO state
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: AI3 voltage (V)
Bit07: Count value
Bit08: Length value
Bit09: PLC stage
Bit10: Load speed display
Bit11: PID reference
Bit12: Reserved
51 Modifiable
in any states
F7‑06 63238 STO software version Modification
prohibited
F7‑07 63239 Heatsink temperature
of IGBT
‑20.0°C to +120.0°C Model
dependent
°C Modification
prohibited
F7‑08 63240 Product SN 01000 Model
dependent
Modification
prohibited
F7‑09 63241 Accumulative running
time
065535 h Model
dependent
h Modification
prohibited
F7‑10 63242 Performance software
version
Model
dependent
Modification
prohibited
F7‑11 63243 Function software
version
Model
dependent
Modification
prohibited
F7‑12 63244 Accumulative power‑
on time
065535 h Model
dependent
h Modification
prohibited
F7‑13 63245 Accumulative power
generation
065535 kWh Model
dependent
kWh Modification
prohibited
F7‑14 63246 Accumulative power
consumption
065535 kWh Model
dependent
kWh Modification
prohibited
F7‑15 63247 Performance software
temporary version
Model
dependent
Modification
prohibited
F7‑16 63248 Function software
temporary version
Model
dependent
Modification
prohibited
F8‑00 63488 Jog frequency 0.00655.35 Hz 2.00 Hz Modifiable
in any states
F8‑01 63489 Jog acceleration time 0.0s to 6500.0s 20.0 s Modifiable
in any states
F8‑02 63490 Jog deceleration time 0.0s to 6500.0s 20.0 s Modifiable
in any states
F8‑03 63491 Acceleration time 2 0.0s to 6500.0s Model
dependent
s Modifiable
in any states