EasyManua.ls Logo

Inovance MD800 Series - Page 94

Inovance MD800 Series
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Trial Run
‑93‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F8‑04 63492 Deceleration time 2 0.0s to 6500.0s Model
dependent
s Modifiable
in any states
F8‑05 63493 Acceleration time 3 0.0s to 6500.0s Model
dependent
s Modifiable
in any states
F8‑06 63494 Deceleration time 3 0.0s to 6500.0s Model
dependent
s Modifiable
in any states
F8‑07 63495 Acceleration time 4 0.0s to 6500.0s Model
dependent
s Modifiable
in any states
F8‑08 63496 Deceleration time 4 0.0s to 6500.0s Model
dependent
s Modifiable
in any states
F8‑09 63497 Jump frequency 1 0.00655.35 Hz 0.00 Hz Modifiable
in any states
F8‑10 63498 Jump frequency 2 0.00655.35 Hz 0.00 Hz Modifiable
in any states
F8‑11 63499 Jump frequency band 0.005.00 Hz 0.00 Hz Modifiable
in any states
F8‑12 63500 Jump frequency
during acceleration/
deceleration
0: Disabled
1: Enabled
0 Modifiable
in any states
F8‑13 63501 Forward/Reverse run
switchover dead‑zone
time
0.0s to 3000.0s 0.0 s Modifiable
in any states
F8‑14 63502 Reverse run 0: Allowed
1: Prohibited
0 Modifiable
in any states
F8‑15 63503 Running mode when
frequency reference
lower than frequency
lower limit
0: Run at frequency lower
limit
1: Stop
2: Run at zero speed
0 Modifiable
in any states
F8‑17 63505 External fault NO
input mode
0: Valid at any time
1: Valid only during
running
0 Modifiable
only at stop
F8‑18 63506 External fault NC
input mode
0: Valid at any time
1: Valid only during
running
0 Modifiable
only at stop
F8‑19 63507 Accumulative power‑
on time threshold
065000 h 0 h Modifiable
in any states
F8‑20 63508 Accumulative running
time threshold
065000 h 0 h Modifiable
in any states
F8‑21 63509 Startup protection 0: Disabled
1: Enabled
0 Modifiable
in any states
F8‑22 63510 Frequency detection
value 1 (FDT1)
0.00655.35 Hz 50.00 Hz Modifiable
in any states
F8‑23 63511 Frequency detection
hysteresis 1 (FDT1)
0.00 to F8‑22 2.50 Hz Modifiable
in any states

Other manuals for Inovance MD800 Series