94
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F8‑24 63512 Frequency detection
value 2 (FDT2)
0.00655.35 Hz 50.00 Hz Modifiable
in any states
F8‑25 63513 Frequency detection
hysteresis 2 (FDT2)
0.00655.35 Hz 2.50 Hz Modifiable
in any states
F8‑26 63514 Frequency detection
frequency
0.00655.35 Hz 2.50 Hz Modifiable
in any states
F8‑27 63515 Detection value 1 of
any frequency
reached
0.00655.35 Hz 50.00 Hz Modifiable
in any states
F8‑28 63516 Detection frequency 1
of any frequency
reached
0.00 to F8‑28 2.50 Hz Modifiable
in any states
F8‑29 63517 Detection mode of
any frequency reach 1
0: Detected at any time
1: Not detected during
acceleration/deceleration
0 Modifiable
only at stop
F8‑30 63518 Detection value 2 of
any frequency
reached
0.00655.35 Hz 50.00 Hz Modifiable
in any states
F8‑31 63519 Detection frequency 2
of any frequency
reached
0.00 to F8‑28 2.50 Hz Modifiable
in any states
F8‑32 63520 Detection mode of
any frequency reach 2
0: Detected at any time
1: Not detected during
acceleration/deceleration
0 Modifiable
only at stop
F8‑35 63523 Switchover frequency
of acceleration time 1
and acceleration time
2
0.00655.35 Hz 0.00 Hz Modifiable
in any states
F8‑36 63524 Switchover frequency
of deceleration time 1
and deceleration time
2
0.00655.35 Hz 0.00 Hz Modifiable
in any states
F8‑37 63525 Set highest priority to
JOG function
0: Disabled
1: Enabled
0 Modifiable
only at stop
F8‑38 63526 Zero current detection
level
0.0% to 300.0% 5.0 % Modifiable
in any states
F8‑39 63527 Zero current detection
delay
0.01s to 600.00s 0.10 s Modifiable
in any states
F8‑40 63528 Output overcurrent
threshold
0.0% to 300.0% 200.0 % Modifiable
in any states
F8‑41 63529 Output overcurrent
detection delay
0.00s to 600.00s 0.00 s Modifiable
in any states
F8‑42 63530 Detection value 1 of
any current reached
0.0% to 300.0% 100.0 % Modifiable
in any states
F8‑43 63531 Detection width 1 of
any current reached
0.0% to 300.0% 0.0 % Modifiable