7
Out3 Close output function No output signal
Out4 Close output function No output signal
C331
Out1 Open overload control function Output overload
control signal
Out2 Open compliance control function Output compliance
control signal
Out3 Open underload control function Output underload
control signal
Out4 Open stable control function Output stable control
signal
C332
Out1 Weight>=C13 instant connection Feeding control
signal
Out2 Weight<=C14 instant connection Feeding control
signal
Out3 OUT1OUT2 close When OUT1OUT2
connect will output
alarm signal,
connect with buzzer
Out4 Weight<=C14 constant
connection
Weight>=C13 disconnect
Feeding start and
stop
C333 Preserved, no function.
For example:
Check weigher application. Connect indicator with yellow, green, red 3
lights. Yellow light on when overload, if ok the green light on. If
underload red light on. And can connect with buzzer. There would be
alarm remind when overload.
C33=2 Feeding control application
For hopper scales. The target is between is 50~500kg, the Output
card can perform open and close feeding valve.
Parameter setting C13=500kg C14=50kg
C13=500kg upper limit , close feeding valve
C14=50kg lower limit, open feeding valve.