10.10 Faults
10.11 Fault codes
If the fault LED is flashing, the boiler controller has detected a fault. A fault code will be
indicated on the main display.
Once the fault has been rectified the boiler controller can be restarted.
Press the reset key on the operating panel.
The following faults are distinguished
Main display
Display Fault Possible Solution
10, 11, 12,
13, 14
Sensor fault S1
Check wiring for break
Replace S1
20, 21, 22,
23, 24
Sensor fault S2
Check wiring for break
Replace S2
0 Sensor fault after self check
Replace S1 and/or S2
1 Temperature too high
Air in installation
Pump not running
Unsufficient flow in installation, radiators closed, pump setting too low
2 S1 and S2 interchanged
Check cable loom
Replace S1 or S2
4 No flame signal
Gas tap closed
No or incorrect ignition gap
Gas supply pressure too low or falling
Gas valve or ignition unit not powered
5 Poor flame signal
Condensate drain blocked
Check adjustment of gas valve
Cheack for earth fault
6 Flame detection fault
Replace ignition cable + spark plug cap
Replace ignition unit
Replace boiler controller
8 Incorrect fan speed
Fan catching on casing
Wiring between fan and casing
Check wiring for poor wire contact
Replace fan*
29,30 Gas valve relay faulty
Replace boiler controller
CAUTION
Always use original Intergas spare parts when replacing
components.
Failure to fit the sensors S1 and/or S2, or to fit them correctly can
result in serious damage.
10.12 Other faults
10.12.1 Burner does not ignite
Possible causes: Solution:
Gas tap is closed.
Open gas tap.
No
Air in the gas pipe. Remove air form gas pipe.
No
Gas supply pressure too low. Contact the gas supply company.
No
No ignition.
Replace ignition electrode.
CAUTION
* The boiler is equipped with a non-return valve (A),
positioned above the fan. Ensure the non-return valve is
repositioned correctly when replacing the fan.