KNX Universal Interface
Product Manual
©2019 INTERRA 8 PM190207005BEN
2. GENERAL PARAMETERS
There are some safety general parameters such as
“Debouncing” and “Module Alive Beacon”. Using
these parameters it is possible to know weather the
device is working correctly.
PARAMETER
DESCRIPTION
VALUES
Debouncing
This function set a common debouncing duration
for every channel. The duration of the selected
option will be used to detect the presence of the
signal to chance its state.
50 ms
100 ms
150 ms
200 ms
250 ms
Module Alive Beacon
This parameter allows sending the value “true”
periodically while the module is running.
Disabled
Enabled
Module Alive Beacon Interval
(sec)
1
This parameter determines the Module Alive
Beacon sending period.
3600 (1…65535)
1
This parameter is only visible when the parameter “Module Alive Beacon” is set to “Enabled”
The following objects can be used through the general function:
OBJ NAME
FUNCTION
TYPE
FLAG
General
Alive Beacon
1 bit
CRT
This object is only visible when the “Module Alive Beacon function is enabled. Via the group address linked,
the value “true” is sent while the module is running.