95
Matrix Mono
Part 3 - Installaon and Field Sengs
Matrix Mono
94
Inventor Matrix Mono Engineering Data Book
Ta-adj is an correction value for Ta.
SOLAR INPUT sets whether solar control signal is connected to hydronic PCB.
(0=NON; 1=CN18; Tsolar 2=CN11SL1SL2)
F-PIPE LENGTH sets the length of refrigerant pipes between outdoor unit and indoor unit.
RT/Ta_PCB sets whether M-kit is valid.
Pump silent mode can decrease water pump maximum output by 5% in order to decrease the noise of heat pump.
7.19 CASCADE SET
MENU > FOR SERVICEMAN > CASCADE SET
Figure 3-7.51:CASCADE SET
PER_START sets the start-up percentage of multiple units for the first time start-up after power on. For example:
Total units PER_START Starting units
6 50% 3
6 30% 2
TIME_ADJUST sets the judgment period of adding and subtracting units
ADDRESS RESET resets the address code of unit.( “FF” is an invalid address code.) Normally, program will set the address for each
unit automatically, only when unit lost address and Hd error code appears then we need to use this function. After setting the
address, you need to press the “UNLOCK” key to confirm.
7.20 HMI ADDRESS SET
MENU > FOR SERVICEMAN > HMI ADDRESS SET
Figure 3-7.52: HMI ADDRESS SET
HMI SET sets the wired controller is master or slave. (0=MASTER, 1=SLAVE)
When HMI SET is set to SLAVE, the controller can only switch the operation mode, turn on or off, set the temperature, and
cannot set other parameters and functions.
HMI ADDRESS FOR BMS sets the HMI address code for BMS.(only valid for master controller)
16 CASCADE SET
20%
5 MIN
FF
ADJUST
16.1 PER_START
16.2 TIME_ADJUST
16.3 ADDRESS RESET
Go to MENU> FOR SERVICEMAN> 17.HMI ADDRESS SET
17 HMI ADDRESS SET
MASTER
0
ADJUST
HMI SET
HMI ADDRESS FOR BMS
Matrix Mono
95
Part 3 - Installation and Field Settings
8 Operation parameter
MENU > OPERATION PARAMETER
This menu is for installer or service engineer reviewing the operation parameters. There are nine pages for the operating
parameter as following
Figure 3-9.1: Operation parameter
OPERATION PARAMETER
#01
OPERATE MODE COOL
ADDRESS
SV1 STATE ON
ONLINE UNITS NUMBER 1
SV2 STATE OFF
SV3 STATE OFF
PUMP_I ON
1/9
OPERATION PARAMETER
#01
PUMP-C OFF
ADDRESS
PUMP-S OFF
PUMP-O OFF
PUMP-D OFF
PIPE BACKUP HEATER OFF
TANK BACKUP HEATER ON
2/9
OPERATION PARAMETER
#01
T1 LEAVING WATER TEMP. 35°C
ADDRESS
WATER FLOW 1.72m
3
/h
GAS BOILER OFF
HEAT PUMP CAPACTIY 11.52kW
POWER CONSUM. 1000kWh
Ta ROOM TEMP 25°C
3/9
OPERATION PARAMETER
#01
Tw2 CIRCUIT2 WATER TEMP. 35°C
ADDRESS
TIS’ C1 CLIMATE CURVE TEMP. 35°C
T5 WATER TANK TEMP. 53°C
TIS2’ C2 CLIMATE CURVE TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
TW_I PLATE W-OUTLET TEMP. 30°C
4/9
OPERATION PARAMETER
#01
Tbt2 BUFFERTANK_LOW TEMP. 35°C
ADDRESS
IDU SOFTWARE 01-09-2019V01
Tbt1 BUFFERTANK_UP TEMP. 35°C
5/9
Tsolar 25°C
OPERATION PARAMETER
#01
COMP.CURRENT 12A
ADDRESS
COMP.FREQENCY 24Hz
ODU MODEL 6kW
COMP.RUN TIME 54 MIN
COMP.TOTAL RUN TIME 1000Hrs
EXPANSION VALVE 200P
6/9
OPERATION PARAMETER
#01
IDU TARGET FREQUENCY 46Hz
ADDRESS
FREQUENCY LIMITED TYPE 5
FAN SPEED 600R/MIN
SUPPLY VOLTAGE 230V
DC GENERATRIX VOLTAGE 420V
DC GENERATRIX CURRENT 18A
7/9
OPERATION PARAMETER
#01
TW_I PLATE W-INLET TEMP. 30°C
ADDRESS
T2 PLATE F-OUT TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
T2B PLATE F-IN TEMP. 35°C
Th COMP. SUCTION TEMP. 5°C
Tp COMP. DISCHARGE TEMP. 75°C
8/9
OPERATION PARAMETER
#01
T4 OUTDOOR AIR TEMP. 5°C
ADDRESS
TF MODULE TEMP. 55°C
T3 OUTDOOR EXCHARGE TEMP. 5°C
P1 COMP. PRESSURE 2300kPa
ODU SOFTWARE 01-09-2018V01
HMI SOFTWARE 01-09-2018V01
9/9