EasyManuals Logo
Home>INVT>DC Drives>CHV Series

INVT CHV Series User Manual

INVT CHV Series
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Detailed Function Description
43
Function
Code
Name Description
Setting
Range
Factory
Setting
P0.03
Frequency
A command
source
0: Keypad
1: AI1
2. AI3
3: HDI1
4:Simple PLC
5. Multi-Step speed
6: PID
7: Communication
0~7 0
0: Keypad: Please refer to description of P0.10
1: AI1
2: AI3
The reference frequency is set by analog input. AI1 is 0~10V voltage input terminal,
while AI3 is -10V~10V voltage input.
Notice:
z For detailed relationship between analogue input voltage and frequency,
please refer to description of P5.15~P5.19.
z 100% of AI is corresponding to maximum frequency.
3: HDI1
The reference frequency is set by high speed pulse input.
Pulse specification : pulse voltage range 15~30V, and pulse frequency range 0.0~50.0
kHz.
Notice: High speed pulse can only be input through HDI. P5.00 must be set to be 0
(HDI), and P5.35 must be set to be 0 (reference input). For detailed relationship
between HDI input and frequency, please refer to description of P5.37~P5.41.
4: Simple PLC
User can set reference frequency, hold time, running direction of each step and
acceleration/deceleration time between steps. For details, please refer to description of
PA group.
5: Multi-steps speed
The reference frequency is determined by PA group. The selection of steps is
determined by combination of multi-step speed terminals.
Notice:
z Multi-step speed mode will enjoy priority in setting reference frequency if
P0.03 is not set to be 4 or 5. In this case, only step 1 to step 15 are available.
z If P0.03 is set to be 5, step 0 to step 15 can be realized.
z Jog has highest priority.