Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.03
PUMP
A
SEL
0~4
0~4
0
P8.04
PUMP
B
SEL
0~4
0~4
0
P8.05
PUMP
C
SEL
0~4
0~4
0
P8.06
PUMP
D
SEL
0~4
0~4
0
P8.07
PUMP
E
SEL
0~4
0~4
0
P8.08
PUMP
F
SEL
0~4
0~4
0
P8.09
PUMP
G
SEL
0~4
0~4
0
0:
Pump
invalid.
The
corresponding
pump
is
not
installed
or
does
not
work.
1:
Variable
frequency
CON
pump
The
corresponding
pump
is
started
by
inverter.W
hen
it
can
not
be
switched,the
pump
can
adjust
the
output
automatically
as
variable
adjust
pump
to
make
sure
that
the
pressure
to
be
constant.
When
fulfilling
the
switching
requirement,
the
pump
will
switch
to
run
at
grid-frequency
or
stop
running.
NOICE:
When
P8.01=0,
and
A-G
pumps
are
set
as
variable
frequency
pumps,the
corresponding
pump
will
be
invalid.
2:
Power
frequency
pump
The
pump
only
run
at
grid-frequency,
when
the
capacity
of
power
network
is
big
enough
and
the
power
of
pump
is
less
than
15kW,
the
pumps
will
be
started
with
total
voltage
directly.If
the
power
of
pump
is
greater
than
18.kW
,
it
is
suggested
to
start
with
buck

Table of Contents