P8.19
CLOSE
DELAY
0.1~9.9%
0.1~9.9
0.5s
P8.20
TRIP
DELAY
0.1~9.9%
0.1~9.9
0.5s
It’s
considered
that
there
are
mechanical
delay
time
when
contactor
closes
or
opens,even
more
there
are
remanence
when
vairale
frequency
pump
switch
to
run
at
grid
frequency
which
may
make
the
action
failure.
The
parameters
above
are
used
to
solve
these
problems.
1:
Before
inverter
enables
the
next
available
frequency
pump,it
will
send
contactor
closing
command,
there
are
time
difference
between
command
has
been
sent
and
the
inverter
starts
to
output
by
reason
of
mechanical
delay,that’s
contactor
closing
time.
2:
The
contactor
opening
time
is
time
defferece
from
the
inverter
outputs
coast
to
stop
command
to
inverter
outputs
grid-frequency
contactor
closing
command.it
normally
used
for
which
the
power
of
pump
is
greater
than
45kW
and
the
variable-frequency
pump
needs
to
be
switched
to
run
at
grid
frequency,It
can
minish
switching
current
and
improve
the
success
percentage
of
switching.
Function
Code
Name
Description
0:
Dormancy
enabled
Setting
Range
Factory
Setting
P8.21
PID
SLEEP
SEL
AW
OKE
1:
Running
at
lower
limit