Setting
PA.03
CURR
20.0%~120.0%
20.0~120.0
100.0%
Figure
6.18
Motor
overload
protection
curve.
The
value
can
be
determined
by
the
following
formula:
Motor
overload
protection
current
=
(motor
rated
current
/
inverter
rated
current)
*
100%.
Notice:
This
parameter
is
normally
used
when
rated
power
of
inverter
is
greater
than
rated
power
of
motor.
76
DIEN DAN BIEN TAN HTTP://BIENTAN.HNSV.COM
CHV160A
series
special
inverter
for
water
supply
Motor
overload
protection
time:
60s
with
200%
of
rated
current.
For
details,
please
refer
to
above
figure.