Inspect
whether
the
three-phase
rectify
bridge
is
in
good
condition
or
not.
If
the
rectification
bridge
is
burst
out,
ask
for
support.
Check
the
CHARGE
light.
If
the
light
is
off,
the
fault
is
mainly
in
the
rectify
bridge
or
the
buffer
resistor.
If
the
light
is
on,
the
fault
may
be
lies
in
the
switching
power
supply.
Please
ask
for
support.
Power
supply
air
switch
trips
off
when
power
on:
Inspect
whether
the
input
power
supply
is
grounded
or
short
circuit.
Please
solve
the
problem.
Inspect
whether
the
rectify
bridge
has
been
burnt
or
not.
If
it
is
damaged,
ask
for
support.
Motor
doesn’t
move
after
inverter
running:
Inspect
if
there
is
balanced
three-phase
output
among
U,
V,
W.
If
yes,
then
motor
could
be
damaged,
or
mechanically
locked.
Please
solve
it.
If
the
output
is
unbalanced
or
lost,
the
inverter
drive
board
or
the
output
module
may
be
damaged,
ask
for
support..
Inverter
displays
normally
when
power
on,
but
switch
at
the
input
side
trips
when
running:
Inspect
whether
the
output
side
of
inverter
is
short
circuit.
If
yes,
ask
for
support.
Inspect
whether
ground
fault
exists.
If
yes,
solve
it.
If
trip
happens
occasionally
and
the
distance
between
motor
and
inverter
is
too
far,
it
is
recommended
to
install
output
AC
reactor.
93