Notice:
Be
sure
that
the
electric
polarity
of
(+)
(-)
terminals
is
right;
it
is
not
allowed
to
connect
(+)
with
(-)
terminals
directly,
Otherwise
damage
or
fire
could
occur.
4.4.3
Wiring
at
motor
side
of
main
circuit
Output
Reactor
When
the
distance
between
inverter
and
motor
is
more
than
50m,
inverter
may
be
tripped
by
over-current
protection
frequently
because
of
the
large
leakage
current
resulted
from
the
parasitic
capacitance
with
ground.
And
the
same
time
to
avoid
the
damage
of
motor
insulation,
the
output
reactor
should
be
installed.
Output
EMC
filter
EMC
filter
should
be
installed
to
minimize
the
leakage
current
caused
by
the
cable
and
minimize
the
radio
noise
caused
by
the
cables
between
the
inverter
and
cable.
Just
see
the
following
figure.
Figure
4.9
W
iring
at
motor
side.
4.4.4
Wiring
of
regenerative
unit
Regenerative
unit
is
used
for
putting
the
electricity
generated
by
braking
of
motor
to
the
grid.
Compared
with
traditional
3
phase
inverse
parallel
bridge
type
rectifier
unit,
regenerative
unit
uses
IGBT
so
that
the
total
harmonic
distortion
(THD)
is
less
than
4%.
Regenerative
unit
is
widely
used
for
centrifugal
and
hoisting
equipment.