Page #135 background imageLoading...
Page #135 background image
Goodrive300 Series VFD Basic operation instruction
130
Calculate
i
M
ACR
excitation
current
Flux
linkage
detection
Current
detection
Position
observation
Speed
identification
Voltage
detection
ACR
torque current
Calculate
i
T
Park
Transformation
PWM
pulse
Rectifying
bridge
Inverter
bridge
Motor
Park
Transformation
Clark
transformation
φ
+
-
+
+
-
U
V
U
W
Uu
i
U
i
V
i
W
U
V
U
W
Uu
i
M
i
T
w
r
1w
r
φ
i
T
R S T
-
Function
code
Name
Detailed instruction of parameters
Default
value
P00.00
Speed control mode
0: Sensorless vector control mode 0
(apply to AM and SM)
1: Sensorless vector control mode 1
(applying to AM)
2: SVPWM control
1
P00.15
Motor parameter
autotuning
0: No operation
1: Rotating autotuning
2: Static autotuning 1 (autotune all motor
parameters)
3: Static autotuning 2 (autotune some of
the motor parameters)
0
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P03.00
Speed loop proportional
gain1
0200.0
20.0
P03.01
Speed loop integral time1
0.00010.000s
0.200s
P03.02
Low switching
frequency
0.00HzP03.05
5.00Hz
P03.03
Speed loop proportional
gain 2
0200.0
20.0
P03.04
Speed loop integral time 2
0.00010.000s
0.200s
P03.05
High switching
frequency
P03.02P00.03 (Max. frequency)
10.00Hz
P03.06
Speed loop output filter
08 (corresponding to 02
8
/10ms)
0