11: Decreasing frequency setting
(DOWN)
12: Cancel the frequency change setting
13: Shift between A setting and B setting
14: Shift between combination setting
and A setting
15: Shift between combination setting
and B setting
0x000–0x1223
LED ones: frequency enable selection
0: Both ∧ / ∨ keys and digital
potentiometer adjustments are valid
1: Only ∧/∨ keys adjustment is valid
2: Only digital potentiometer adjustments
is valid
3: Neither ∧ / ∨ keys nor digital
potentiometer adjustments are valid
LED tens: frequency control selection
0: Only valid when P00.06=0 or
P00.07=0
1: Valid for all frequency setting manner
2: Invalid for multi-step speed when
multi-step speed has the priority
LED hundreds: action selection during
stopping
0: Setting is valid
1: Valid during running, cleared after
stopping
2: Valid during running, cleared after
receiving the stop command
LED thousands: ∧/∨ keys and digital
potentiometer Integral function
0: The Integral function is valid
1: The Integral function is invalid