Goodrive300 Series VFD Fault tracking
192
parameters from autotune and
the standard parameter is huge
Autotune overtime
Check the motor connection and
set the parameter.
Check if the upper limit frequency
is above 2/3 of the rated frequency.
Error of controlling the write
and read of the parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control panel
PID feedback
outline fault
PID feedback offline
PID feedback source
disappear
Check the PID feedback signal
Check the PID feedback source
Braking circuit fault or damage
to the braking pipes
The external braking resistor
is not sufficient
Check the braking unit and
change new braking pipe
Increase the braking resistor
The actual running time of the
VFD is above the internal
setting running time.
Ask for the supplier and adjust the
setting running time.
The VFD will report overload
pre-alarm according to the set
value.
Check the load and the overload
pre-alarm point.
Keypad
communication
fault
The connection of the keypad
wires is not good or broken.
The keypad wire is too long
and affected by strong
interference.
There is circuit fault on the
communication of the keypad
and main board.
Check the keypad wires and
ensure whether there is mistake.
Check the environment and avoid
the interference source.
Change the hardware and ask for
service.
Parameters
uploading fault
The connection of the keypad
wires is not good or broken.
The keypad wire is too long
and affected by strong
interference.
There is circuit fault on the
communication of the keypad
and main board.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask for
service.
Change the hardware and ask for
service.
The connection of the keypad
wires is not good or broken.
Check the keypad wires and
ensure whether there is mistake.