Goodrive350 series high-performance multi-function inverter  Chapter 7 
-224- 
Exception occurred to 
resistor; 
Long-time overload running 
or exception occurred 
sensor is proper; 
Check the motor and perform 
maintenance on the motor 
Safe torque off function is 
enabled by external forces 
Exception occurred 
to safe circuit of 
channel H1 
The wiring of STO is 
improper; 
Fault occurred to external 
switch of STO; 
Hardware fault occurred to 
safety circuit of channel H1 
Check whether terminal wiring 
of STO is proper and firm 
enough; 
Check whether external switch 
of STO can work properly; 
Replace the control board 
Exception occurred 
to channel H2 safe 
circuit 
The wiring of STO is 
improper; 
Fault occurred to external 
switch of STO; 
Hardware fault occurred to 
safety circuit of channel H2 
Check whether terminal wiring 
of STO is proper and firm 
enough; 
Check whether external switch 
of STO can work properly; 
Replace the control board 
Exception occurred 
to channel H1 and 
channel H2 
Hardware fault occurred to 
STO circuit 
Replace the control board 
Safety code FLASH 
CRC check fault 
Replace the control board 
Repetitive extension 
card type 
The two inserted extension 
cards are of the same type 
Users should not insert two 
cards with the same type; 
check the type of extension 
card, and remove one card 
after power down 
No electric level variation 
occurred to UVW signal 
Check the wiring of UVW; 
Encoder is damaged 
Failed to identify the 
extension card in 
card slot 1 
There is data transmission in 
interfaces of card slot 1, 
however, it cannot read the 
card type 
Confirm whether the extension 
card inserted can be 
supported; 
Stabilize the extension card 
interfaces after power down, 
and confirm whether fault still 
occurs at next power-on; 
Check whether the insertion 
port is damaged, if yes, replace